325
Learning Protection Features
To receive PTC signal at V1 input terminal, set PRT-35 (Thermal InSrc) to ‘0 (Thermal In)’ and set the
Analog1 input selection switch (SW3) to T1.
To receive PTC signal at I2 input terminal, set PRT-35 (Thermal InSrc) to ‘1 (V2)’ and set SW 4
(Analog2 input selection switch) to V2. The sensor does not operate if SW4 is set to ‘I2’.When the
inverter detects a motor overheat, motor overheat trip occurs with internal delay time. The trip
delay time is not reset instantly when the trip condition is released, but it only decreases as time
passes.
6.1.3
Overload Early Warning and Trip
Group Code
Name
LCD Display
Parameter Setting
Setting range
Unit
PRT
17
Overload warning
selection
OL Warn Select
1
Yes
0–1
-
18
Overload warning
level
OL Warn Level
110
30–150
%
19
Overload warning
time
OL Warn Time
10.0
0–30
sec
20
Motion at overload
trip
OL Trip Select
1
Free-Run
-
-
21
Overload trip level
OL Trip Level
120
30–150
%
22
Overload trip time
OL Trip Time
60.0
0–60.0
sec
OUT
31–
35
Multi-function relay
1–5 item
Relay 1–5
5
Over Load
-
-
36
Multi-function
Q1 Define
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...