348
Learning Protection Features
Main Capacitor Life Estimation Detail Settings
Code
Description
PRT-83 CAP.
Diag Perc
Configure the current level of the inverter’s output when capacitance life
examination is in operation. For life examination, the value must be set higher than
0%.
PRT-84 CAP.
Diag
Configure the capacitance life examination mode. This mode is separated into
installing the inverter mode and maintenance mode. To use the capacitance life
examination function, proper setting is required.
Setting
Function
0
None
Do not use capacitance life examination function.
1
CAP. Diag 1
When installing the inverter for the first time,
estimate initial capacitance.
2
CAP. Diag 2
Estimate the capacitance while maintaining the
inverter.
3
CAP. Init
Initialize the estimated value of the capacitance to 0.
PRT-85 CAP.
Level 1
Set the standard level for the capacitance replacement.
PRT-86 CAP.
Level 2
Display estimated capacitance value according to the mode in PRT-84. If this value
is lower than the value set in PRT-85, the warning message”CAP Warning” appears
on the display.
•
Be careful when replacing the battery. Remaining voltage in the battery may cause electric shock.
•
Make sure that the battery doesn’t fall inside of the inverter.
•
The main capacitor life examination is only for reference and cannot be used as an absolute
value.
•
The main capacitor life examination only operates in AUTO mode and when inverter is
stopped.
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...