342
Learning Protection Features
Code
Description
OUT-36 Q1 Define,
OUT-31–35 Relay1–5
When the code value is set to ‘8 (FAN Warning)’, the fan error signal is output
and operation continues. However, when the inverter’s inside temperature
rises above a certain level, output is blocked due to activation of overheat
protection.
6.3.2
Low Voltage Fault Trip
When inverter input power is lost and the internal DC link voltage drops below a certain voltage
level, the inverter stops output and a low voltage trip occurs.
Group Code Name
LCD Display
Parameter Setting
Setting range
Unit
PRT
81
Low voltage trip
decision delay time
LVT Delay
0.0
0–60.0
sec
OUT
31–
35
Multi-function relay
1–5
Relay 1–5
11
Low
Voltage
-
36
Multi-function
output 1
Q1 Define
Low Voltage Fault Trip Setting Details
Code
Description
PRT-81
LVT Delay
If the code value is set to ‘11 (Low Voltage)’, the inverter stops the output first when a
low voltage trip condition occurs, then a fault trip occurs after the low voltage trip
decision time elapses. The warning signal for a low voltage fault trip can be provided
using the multi-function output or a relay. However, the low voltage trip delay time
(LVT Delay time) does not apply to warning signals.
6.3.3
Selecting Low Voltage 2 Fault During Operation
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...