299
Learning Advanced Features
5.44.8.4
Master Follower Interlock
As Interlock signals are sent from Serve Drive, Leader Drive puts together through Communication
Line. Every Trip such as HAND State or OFF State of Serve Drive is processed by Interlock in Leader
Drive .
This is, other Server Drives keep performing Master Follower function except the cases that it is in
HAND/OFF State or there are trips
If Leader Drive is HAND State or OFF state, Master Follower system is not activated.
In case that Pipe Broken and Interlock Trip are caused in Leader Drive, every drive operating is
stopped and Master Follower keeps performing the function except Leader Drive if there is
another Trip.
(Leader Drive executes PID control and overall system control consistently.)
In this operating priority (M1 M2 M3 M4 M5 M6 M7 M8), if interlock3 or any
↔
↔
↔
↔
↔
↔
↔
trip and HAND/OFF State are caused, the motor is activated in this order(M1 M2 M4 M5
↔
↔
↔
M6 M7 M8).
↔
↔
↔
Interlock1
Interlock2
Interlock3
Interlock4
Interlock8
Leader Drive
ID 1
Serve Drive
ID 2
Serve Drive
ID 3
Serve Drive
ID 4
Serve Drive
ID 8
Inverter
Setting
Main
Motor
M1
M2
M3
M4
M8
Sensor
Aux
Motor
Aux
Motor
Aux
Motor
Aux
Motor
Communication
Line
The picture below shows the function in case that M3 becomes HAND/OFF State or interlock and
Trip are caused.(supposing that the priority is not changed),(interlock is the function
corresponding to B terminal(Normal close)).
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...