246
Learning Advanced Features
Starting with power-on:
Set bit 4 to ‘1’ and ADV-10 (Power-on Run) to ‘1
(Yes)’. If inverter input power is supplied while the inverter operation
command is on, the speed search operation will accelerate the motor up to
the frequency reference.
CON-72 SS Sup-
Current
The amount of current flow is controlled during speed search operation
based on the motor’s rated current. If CON-70 (SS mode) is set to ‘1 (Flying
Start-2)’, this code is not visible.
CON-73 SS P-Gain,
CON-74 SS I-Gain
The P/I gain of the speed search controller can be adjusted. If CON-70 (SS
Mode) is set to ‘1(Flying Start-2)’, different factory defaults, based on motor
capacity, are used and defined in DRV-14 (Motor Capacity).
CON-75 SS Block
Time
The block time parameter prevents overvoltage trips due to counter
electromotive force.
Note
If operated within the rated output, the H100 series inverter is designed to withstand instantaneous
power interruptions within 8 ms and maintain normal operation. The DC voltage inside the inverter
may vary depending on the output load. If the power interruption time is longer than 8 ms, a low
voltage trip may occur.
Select the Speed search function (normal acceleration) for a proper re-operation during a free-run.
If the speed search function (normal acceleration) is not selected during the acceleration, an over
current trip or an overload trip may occur.
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...