563
Troubleshooting
LCD Display
Type
Description
the specified value.
Over Current2
Latch
Displayed when the DC circuit in the inverter detects a specified
level of excessive, short circuit current.
External Trip
Latch
Displayed when an external fault signal is provided by the multi-
function terminal. Set one of the multi-function input terminals at
IN-65-71 to ‘4 (External Trip)’ to enable external trip.
BX
Level
Displayed when the inverter output is blocked by a signal provided
from the multi-function terminal. Set one of the multi-function
input terminals at IN-65-71 to ‘5 (BX)’ to enable input block function.
H/W-Diag
Fatal
Displayed when an error is detected in the memory (EEPRom),
analog-digital converter output (ADC Off Set) or CPU watchdog
(Watch Dog-1, Watch Dog-2).
EEP Err: An error in reading/writing parameters due to keypad or
memory (EEPRom) fault.
ADC Off Set: An error in the current sensing circuit
(U/V/W terminal, current sensor, etc.).
NTC Open
Latch
Displayed when an error is detected in the temperature sensor of
the Insulated Gate Bipolar Transistor (IGBT).
Fan Trip
Latch
Displayed when an error is detected in the cooling fan. Set PRT-79
to ‘0’ to activate fan trip (for models below 22 kW capacity).
InFan Trip
Latch
It occurs when an abnormality is detected in the cooling fan inside
the inverter with inverter capacity of 110 kW to 500 kW.
Selecting PRT - 79 code to 0 will work.
Thermal Trip
Latch
Triggered when the input temperature is higher than the
temperature set by the user.
Lost KeyPad
Latch
Triggered when a communication error occurs between the
keypad and the inverter, when the keypad is the command source,
and PRT-11 (Lost KPD Mode) is set to any other value than ‘0’.
Fuse Open
Latch
If an input stage fuse breaks with an inverter of 315 kW or more, a
fault will occur.
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...