The time set at AP2-39 refers to the absolute time that it takes for the pump to decelerate from the
frequency set at AP2-38 to the frequency limit set at ADV-25.
5.17
Load Tuning
Load tuning refers to an operation that detects the load applied to a specific section of the inverter
operation (current and voltage) and creates an ideal load curve for the under load and pump
clean operations. The two set points to define the section are user-definable, and are set at 50%
and 85% of the base frequency (DRV-18 Base Freq) by default. The load tuning result values are
saved at codes AP2-2–AP2-10. These values are user definable as well.
The minimum set point for the load tuning begins at 15% of the base frequency (DRV-18 Base
Freq), and the maximum set point can be set up to the base frequency. If the frequency limit is set
to ‘1 (Yes)’ at ADV-24 (Freq Limit), the range is limited within the frequencies set at ADV-25 (Freq
Limit Lo) and ADV-26 (Freq Limit Hi).
Group Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
AP2
01
Load curve
Tuning
Load Tune
No
0
No
-
1
Yes
02
Load curve Low
Freq
Load Fit
LFreq
30.00
Base Freq*15%–
Load Fit HFreq
Hz
03
Current for Low
Freq
Load Fit
LCurr
40.0
0.0–200.0
%
04
Power for Low
Freq
Load Fit LPwr 30.0
0.0–200.0
%
08
Load curve High
Freq
Load Fit
HFreq
51.00
Load Fit LFreq–
High Freq
Hz
09
Current for High
Freq
Load Fit
HCurr
80.0
0.0–200.0
%
10
Power for High
Freq
Load Fit
HPwr
80.0
0.0–200.0
%
11
Load current for
frequency
Load Curve
Cur
-
-
%
12
Load power for
frequency
Load Curve
Pwr
-
-
%
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...