412
RS-485 Communication Features
•
When PowerOn Resume (COM-96) is set to ‘yes’, value is saved even if the power of the inverter is
disconnected. If PowerOn Resume (COM-96) is set to ‘no’, value is not saved when the power of
the inverter is disconnected.
•
Cannot set the value higher than the maximum frequency (DRV-20). The maximum frequency
can be set by using the keypad. This value can be used when Freq Ref Src (DRV-07) is set to ‘Int
485’.
7.5.3.2
Binary Output
The output point map controlling the inverter from the Metasys-N2 master.
No.
Name
Range
Description
BO1
Stop Command
1: Stop
Stop command
BO2
Run Forward Command 1: Forward Run
Forward run command
BO3
Run Reverse
Command
1: Reverse Run
Reverse run command
BO4
Reset Fault
1: Reset
Fault reset command
BO5
Free-Run Stop
1: Bx
Free-run stop command
7.5.3.3
Analog Input
Metasys-N2 master monitors inverter state.
No.
Name
Unit
Description
AI1
Output Current
Amps
Output current
AI2
Output Frequency
Hz
Output frequency
AI3
Output Speed
RPM
Output speed
AI4
Trip Code
-
Trip code information
(Refer to Common Area parameter address 0h000F)*
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...