204
Learning Advanced Features
Code
Description
exceeds the number set at AP2-33 within the time period set at
AP2-32.
Note
•
When the run prevent feature is active and an operation in the prevented direction is required to
perform a pump clean operation, the inverter operates at the 0 speed for the time set at AP2-24
and AP2-26 (Steady Time).
•
To stop the pump clean operation, press the OFF key on the keypad or turn it off at the terminal
input.
•
If the pump clean operation is configured for terminal input and it is turned on, and if ADV-10
(PowerOn Resume) is set to ‘Yes’, a pump clean operation is performed when the inverter is turned
on.
•
When performing a pump clean operation via terminal input,
-
if the terminal input is turned off instantly after it is turned on (the operation is triggered),
1 pump clean cycle is operated.
-
if ADV-10 (PowerOn Resume) is set to ‘Yes’, and the terminal input is turned off instantly
after it is turned on (the operation is triggered), and if the inverter is turned off during a
pump clean then is turned back on again, the pump clean operation is not resumed
(because the input terminal is not on when the inverter is turned on).
-
if the terminal input is kept on after it is initially turned on, 1 pump clean cycle is
operated.
5.15
Start & End Ramp Operation
This function is used to rapidly accelerate the pump to the normal operating level, or to rapidly
decelerate the pump and stop it. Start & End ramp operation is performed when ADV-24 (Freq
Limit) is set to ‘1 (Yes).’
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
AP2
40
Start & End Ramp
Gradient
Start&End Ramp 0: No
0
No
-
1
Yes
41
StartRampAcc
StartRampAcc
10.0
0–600.0
Sec
42
EndRampDec
EndRampDec
10.0
0–600.0
Sec
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...