158
Learning Advanced Features
5.5
Safe Operation Mode
When the multi-function terminals are configured to operate in safe mode, operation commands
can be entered in the Safe operation mode only. Safe operation mode is used to safely and
carefully control the inverter through the multi-function terminals.
Group
Code
Name
LCD Display
Parameter Setting
Setting
Range
Unit
ADV
70
Safe operation
selection
Run En Mode
1
DI Dependent 0-1
-
71
Safe operation
stop mode
Run Dis Stop
0
Free-Run
0–2
-
72
Safe operation
deceleration
time
Q-Stop Time
5.0
0.0–600.0
sec
IN
65–71
Px terminal
configuration
Px Define(Px: P1–
P7)
15 RUN Enable
0-55
-
Safe Operation Mode Setting Details
Code
Description
IN-65–71 Px Define
From the multi-function terminals, select a terminal to operate in safe
operation mode and set it to ‘15 (RUN Enable)’.
ADV-70 Run En
Mode
Setting
Function
0
Always Enable
Enables safe operation mode
1
DI Dependent
Recognizes the operation command from a multi-
function input terminal.
ADV-71 Run Dis
Stop
Set the operation of the inverter when the multi-function input terminal in safe
operation mode is off.
When the safety operation mode terminal signal is given, the inverter
decelerates based on the settings at the Q-Stop time. The inverter decelerates
and stops based on the deceleration time (Dec Time) settings if the run
command is off.
Setting
Function
1
Free-Run
Blocks the inverter output when the multi-function
terminal is off.
2
Q-Stop
The deceleration time (Q-Stop Time) used in safe
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...