297
Learning Advanced Features
St art Freq 1
St art Freq 3
Out Freq
High Freq
t
M1 OutFreq
M2 OutFreq
St op Freq 2
St art Freq 2
St op Freq 3
M3 OutFreq
Run Cmd
FeedBack
PI D Reference
M1 Cmd Freq
PID Ctrl
M2 Cmd Freq
M3 Cmd Freq
Main Motor
M1, M2
M3
M2
PID Ctrl
PID Ctrl
Main Motor
Main Motor
Main
Motor
Aux Motor
Main Motor
Aux Motor
Aux Motor
Aux Motor
Aux Motor
Aux Motor
PI D Output
PI D Limit High
M1
M1, M2
A condition that extra Aux Motor is turned on
.
After a real operating frequency reaches the frequency set in Start Freq belonging to the next
priority number and the time set in AP1-53(Aux Start DT) passes, AP1-44(Aux Motor Run) increases
(+1). In addition, Aux Motor with the next priority of Main Motor is turned on and the new
operating Aux Motor becomes Main Motor. Operating motors can be controlled together by PID.
It is possible to check the priority in [AP1-45/46 Aux Priority].
A condition that Aux Motor is turned off.
If the real operating frequency of Main Motor is lower than the frequency set in Stop Freq, AP1-
44(Aux Motor Run) decreases(-1) after the time set in AP1-54(Aux Stop DT) and the present Main
Motor becomes Aux Motor, decelerating based on time of [DRV-04 Dec Time] until 0Hz.
At the same time, the rest of operating motors last PID control. It is possible to check the priority in
[AP1-45/46 Aux Priority].
5.44.8.3
Re-arrangement of priority based on operating time.
The priority of each Motor is arranged automatically based on operating time.
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...