182
Learning Advanced Features
Group Code
Name
LCD Displays
Parameter Setting
Setting Range
Unit
13
PID wakeup 2 delay
time
PID WakeUp2
DT
20.0
0–6000.0
sec
14
PID wakeup 2 value
PID
WakeUp2Dev
20.00
0–Unit Band
Unit
20
Soft Fill options
Soft Fill Sel
0
No
0–1
-
PID Operation Sleep Mode Setting Details
Code
Description
AP1-05 Sleep Bst Set
Sets the sleep boost volume. Feedback must reach the boost level
(PID ReSleep Bst Set) for the inverter to enter the Sleep
Mode.
AP1-06 Sleep Bst Freq
Sets the inverter operation frequency to reach sleep boost level.
AP1-07 PID Sleep1 DT
AP1-11 PID Sleep2 DT
AP1-08 PID Sleep1Freq
AP1-12 PID Sleep2Freq
If the operating frequency stays below the frequencies set at AP1-08
and AP1-12 for the set times at AP1-07 and AP1-11, the inverter
accelerates to the PID sleep boost frequency (PID Sleep Bst Freq).
Then, when the feedback reaches the value set at the boost level, the
inverter enters standby mode.
AP1-09 PID WakeUp1 DT
AP1-13 PID WakeUp2 DT
AP1-10 PID WakeUp1Dev
AP1-14 PID WakeUp2Dev
Sets the reference for PID operation in PID sleep mode. PID operation
resumes when PID feedback variation (from the PID reference)
exceeds the values set at AP1-10 and AP1-14, and maintains the
condition for times set at AP1-09 or AP1-13.
IN-65–71
P1–7 Define
When the PID Sleep Wake 2 terminal is set and input, PID operation
sleep mode is operated based on the parameter settings at AP1-11–
14.
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...