255
Learning Advanced Features
Code
Description
ADV-64 Fan Control
Settings
Description
0
During Run
The cooling fan runs when the power is supplied to the
inverter and the operation command is on. The cooling
fan stops when the power is supplied to the inverter and
the operation command is off. When the inverter heat
sink temperature is higher than its set value, the cooling
fan operates automatically regardless of its operation
status.
1
Always On
Cooling fan runs constantly if the power is supplied to
the inverter.
2
Temp
Control
With power connected and the run operation command
on: if the setting is in Temp Control, the cooling fan will
not operate unless the temperature in the heat sink
reaches the set temperature.
Note
Despite setting ADV-64 to ‘0 (During Run)’, if the heat sink temperature reaches a set level by current
input harmonic wave or noise, the cooling fan may run as a protective function.
A capacity of 110 kW or more has a small built-in fan installed to cool the internal temperature. The
internal fan controls on / off in conjunction with the operation command of the inverter main control
fan
5.33
Input Power Frequency and Voltage Settings
Select the frequency for inverter input power. If the frequency changes from 60 Hz to 50 Hz, all
other frequency (or RPM) settings, including the maximum frequency, base frequency, etc., will
change to 50 Hz. Likewise, changing the input power frequency setting from 50 Hz to 60 Hz will
change all related function item settings from 50 Hz to 60 Hz.
Group Code Name
LCD Display
Parameter Setting
Setting Range
Unit
BAS
10
Input power frequency
60/50 Hz Sel
0 60 Hz
0–1
-
Set Inverter input power voltage. Low voltage fault trip level changes automatically to the set
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...