349
Learning Protection Features
6.4.2
Fan Life Estimation
The inverter records the amount of time the fan is used and sets off the alarm to replace the fan if
the fan is used longer than the certain period of time.
Group Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
PRT
87
Fan accumulated
time percentage
Fan Time Perc 0.0
0.0–6553.5
%
88
Fan replacement
alarm level
Fan
Exchange
0.0
0.0–100.0
%
CNF
75
Initializing the
accumulation time
of the fan operation
Fan Time Rst
0: No
0
No
1
Yes
OUT
31–35
Relay 1–5 output
Relay 1–5
35
Fan Exchange
-
When PRT-88 value is 0%, Fan Exchange alarm does not occur and user can use the function when
it is set to a value other than 0%
.
Fan Life Estimation Setting Details
Code
Description
PRT-87
Fan Time Perc
Displays the time the fan is used in percentage based on 50,000 hours.
If this value is bigger than the value in PRT-88, the warning message”Fan
Exchange” appears on the display.
PRT-88
Fan Exchange
Displays the life replacement standard of the fan in percentage.
CNF-75
Fan Time Rst
Initializes the accumulation time of the fan operation.
Setting
Function
0
No
Do not initialize the accumulated operation time of the fan.
1
Yes
Initialize the accumulated operation time of the fan.
•
Be careful when replacing the battery. Remaining voltage in the battery may cause electric shock.
•
Make sure that the battery doesn’t fall inside of the inverter.
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...