274
Learning Advanced Features
5.44.1
Multiple Motor Control (MMC) Basic Sequence
Multiple motor control (MMC) is an operation based on PID control. During an MMC operation,
the main and auxiliary motors organically operate together.
During a PID operation, the auxiliary motors are turned on when the inverter frequency reaches
the start frequencies set at AP1-61–65 (Start freq), and the difference between the PID reference
and feedback is bigger than the value set at AP1-50. Then, the auxiliary motors stop operating
when the operation frequency reach the stop frequency set at AP1-70–74 (Stop Freq 1–5) and the
difference between the PID feedback and reference becomes greater than the value set at AP1-50.
AP1-51 Acc Time
AP1-52 Dec Time
Parameters used when AP1-40 is set to ‘Single Ctrl’
When an auxiliary motor starts or stops, the main motor stops the
PID control, and performs general acceleration and deceleration.
When an auxiliary motor starts, the main motor decelerates to the
auxiliary motor deceleration frequency set at AP1-70–74 (Stop Freq
1–5) based on the deceleration time set at AP1-52 (Dec Time).
When the auxiliary motor stops, the main motor accelerates up to
the auxiliary motor restart frequency set at AP1-61–65 (Start Freq 1–
5) based on the acceleration time set at AP1-51 (Acc Time).
AP1-53 Aux Start DT
AP1-54 Aux Stop DT
The auxiliary motors turns on or off after the auxiliary motor stop
delay time or the auxiliary motor restart delay time elapses, or if the
difference between the current reference and the feedback is greater
than the value set at AP1-50 (Actual Pr Diff).
AP1-61–65 Start Freq1–5
Sets the auxiliary motor start frequency.
AP1-70–74 Stop Freq 1–5
Sets the auxiliary motor stop frequency.
AP1-95 AuxRunTime Sel
Selects auxiliary motor to be used in AP1-96 and AP1-97.
AP1-96 AuxRunTime Day
Indicates operating time(day) selected in AP1-95.
AP1-97 AuxRunTime Min
Indicates operating time of auxiliary motors selected in AP1-95.
AP1-98 AuxRunTime Clr
Deletes operating time of auxiliary motors.
OUT-31–35 Relay 1–5
OUT-36 Q1 Define
Configure the output terminals to ’21 (MMC)’ to use the terminals to
control the auxiliary motors. The number of the configured output
terminals determines the total number of auxiliary motors to be
used.
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...