284
Learning Advanced Features
NOTE
Auto change does not work while the auxiliary motors are operating. Auto change is operated only
when all the auxiliary motors are stopped and if all the conditions set for the auto change are met. When
the inverter stops, all motors stop operating, and the auxiliary motor with the highest priority becomes
the starting auxiliary motor. If the inverter power is turned off then turned back on, the auxiliary motor
set at AP1-43 (Starting Aux) becomes the starting auxiliary motor.
The following diagrams depict the auto change operation when AP1-55 (Auto Ch Mode) is set to ‘2
(Main),’ when the inverter operation time exceeds the auto change interval set at AP1-58. If the inverter
operation frequency is below the frequency set at AP1-57, all the auxiliary motors including the start
auxiliary motor are turned off. After the delay time set at AP1-91 (Interlock DT) elapses, the ‘Main’ auto
change is operated. After the ‘Main’ auto change, the auxiliary motor that was turned on after the
starting auxiliary motor becomes the main motor.
In the following diagrams, because auxiliary motor #1 is the starting auxiliary motor. Auxiliary motor #2
becomes the main motor after the auto change. The auxiliary motor on/off operation is identical to that
of Aux Exchange, and the ‘off’ conditions differ based on the FIFO/FILO configuration.
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...