39
Installing
the Inverter
Function
Label
Name
Description
V2/I2
Voltage/current input for
frequency reference input
Used to setup or modify a frequency
reference via analog voltage or current input
terminals.
Switch between voltage (V2) and current (I2)
modes using a control board switch (SW4).
Input current: 0–20 mA
Maximum Input current: 24 mA
Input resistance 249 Ω
TI
Pulse input for frequency
reference input (pulse
train)
Setup or modify frequency references using
pulse inputs from 0 to 32 kHz.
Low Level: 0–0.8 V, High Level: 3.5–12 V
Output/Communication Terminal Labels and Descriptions
Function
Label
Name
Description
Analog
output
AO
Voltage/Current
Output
Used to send inverter output information to external
devices: output frequency, output current, output
voltage, or a DC voltage.
Operate switch (SW5) to select the signal output type
(voltage or current) at the AO terminal.
Output Signal Specifications:
Output voltage: 0–10 V
Maximum output voltage/current: 12 V/10 mA
Output current: 0–20 mA
Maximum output current: 24 mA
Factory default output: Frequency
Terminal
Contacts
Q1
Multi-function
(Open Collector)
Pulse Output
Selects a multi-function output signal or pulse
output, output frequency, output current, output
voltage, DC voltage by selecting one of the outputs.
DC 26 V, 50 mA or less
Pulse output terminal
Output frequency: 0–32 kHz
Output voltage: 0–12 V
EG
Common
Common ground contact for an open collector (with
external power source)
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...