Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
123
4
Device control (DCTRL)
4.3
Automatic restart after mains connection/fault...
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.3
Automatic restart after mains connection/fault...
.../Error/undervoltage/loading of the Lenze setting
In
, the starting performance of the inverter after mains connection, undervoltage, loading
of the Lenze setting as well as a "
" or a "
" reset can be parameterised individually:
4.3.1
"Inhibit at power-on" auto-start option
The auto-start option
"Inhibit at power-on" prevents the change to the "
mains connection if the controller is already enabled at mains connection.
The following three cases describe the behaviour of the inverter after mains connection depending
on whether the controller is enabled and the set auto-start option. Here, it is assumed that after
mains connection, no errors and trouble occur in the inverter and the "EnableOperation" control bit
in the
wDriveControl
is set to "1".
Auto-start option (
Lenze setting
Bit 0
"Inhibit at power-on" auto-start option
1
≡
Inhibit is active
Bit 1 Inhibit at trouble
0
≡
Inhibit is not active
Bit 2 Inhibit at fault
0
≡
Inhibit is not active
Bit 3 Inhibit at undervoltage
1
≡
Inhibit is active
Bit 4
Auto-start option "Inhibit at Lenze setting"
(from version 06.00.00)
1
≡
Inhibit is active
Bit 5 Reserved
0
Bit 6
Bit 7
Note!
In the Lenze setting
, automatic restart after mains connection, undervoltage, and
loading of the Lenze setting is inhibited.
Danger!
If the
"Inhibit at power-on" auto-start option has been deactivated in
, (bit 0 = 0),
the motor can directly start to run if the controller is enabled after mains connection!