8
Basic drive functions (MCK)
8.6
Homing
570
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.6.1.6
Option "Actual MCTRL position received at mains switch-off"
The encoder position can be saved with mains failure protection in the inverter. For this purpose, the
bit 0 has to be set in
•
From version 14.00.00
, the "Actual MCTRL position received at mains switch-off" option can also
be accessed in the »Engineer« via the parameterisation dialog for the basic function
Homing
(depending on the set position encoder system).
• If bit 0 is set in
, the actual position of the motor control is saved in the inverter (not in
the memory module) and thus remains known to the drive control after mains switching.
The following overview shows the actual position after mains connection depending on the setting
/bit 0:
8.6.2
Requesting the operating mode
Request for the "referencing" operating mode by means of the
If the
MCKInterface
is connected upstream to the
Motion Control Kernel
and if the operating mode
is requested at the
wOperationMode
and
bOperationMode_1...8
process
inputs are available.
C02652
bit 0
Reference available
in case of mains
switch-off
(Status bit
"
")
Actual position and status reference
in case of mains switch-on
= 0, 1, 2, 10: Incremental encoder (HTL) or no encoder
0
0
0 incr.
Reference is unknown
1
Reference is unknown
1
0
dnActPos
(mains switch-off)
Reference is unknown
1
Reference available
MCK control word
Bit 31
...
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
OpMode_Bit3
OpMode_Bit2
OpMode_Bit1
OpMode_Bit0
X
...
X
0
0
0
1
X = Status not significant