6
I/O terminals
6.3
Analog terminals
350
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3.1
Parameterising analog input
By clicking on the
button on the
Terminal assignment
tab, you reach the parameterising
dialog for the corresponding analog input:
Short overview of parameters for the analog inputs:
Parameters
Info
Lenze setting
Value Unit
Analog input 1
AIN1: Config.
0: -10V..+10V
AIN1: Offset
0.00 %
AIN1: Gain
1.0000
AIN1: Input voltage
- V
AIN1: Input current
- mA
AIN1: Output value (to application)
- %
PT1 rounding AnalogIn1
10 ms
Resp. to open circuit AIN1
3: TroubleQuickStop
Analog input 2
AIN2: Config.
0: -10V..+10V
AIN2: Offset
0.00 %
AIN2: Gain
1.0000
AIN2: Input voltage
- V
AIN2: Input current
- mA
AIN2: Output value (to application)
- %
PT1 rounding AnalogIn2
10 ms
Resp. to open circuit AIN2
3: TroubleQuickStop
Greyed out = display parameter