Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
279
5
Motor control (MCTRL)
5.11
Encoder/feedback system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
General procedure
(if the encoder is connected to the digital inputs DI1 and DI2)
1. Define the function of the digital inputs DI1 and DI2 in
2. Set the encoder increments in
.
3. Select "1: Encoder signal FreqIn12" in
4. Adapt the filter time of the speed measurement in
.
5. In the case of encoders with a very low resolution (number of increments < 120 increments):
Change the encoder evaluation procedure in
if necessary.
Settings for HTL encoder at DI1/DI2
Fct. DI 1/2 200kHz
• Function of the digital inputs DI1 and DI2
0: DI1(6)=In / DI2(7)=In
FreqIn12: Encoder increment
• If the digital inputs DI1 and DI2 are used as
encoder inputs.
128 Incr./rev.
FreqIn12: Encoder scanning time
• If the digital inputs DI1 and DI2 are used as
encoder inputs.
10 ms
FreqIn12: Encoder filter time
• If the digital inputs DI1 and DI2 are used as
encoder inputs.
1.0 ms
Encoder evaluation method DigIn12 (
2: Comb. encoder method
Actual value - HTL encoder FreqIn12
- rpm
Settings for HTL encoder at DI6/DI7
Fct. DI 6/7 10kHz
• Function of the digital inputs DI6 and DI7
0: DI1(6)=In / DI2(7)=In
FreqIn67: Encoder increment
• If the digital inputs DI6 and DI7 are used as
encoder inputs.
128 Incr./rev.
FreqIn67: Encoder scanning time
• If the digital inputs DI6 and DI7 are used as
encoder inputs.
10 ms
FreqIn67: Encoder filter time
• If the digital inputs DI6 and DI7 are used as
encoder inputs.
1.0 ms
Actual value - HTL encoder FreqIn67
- rpm
Monitoring
Resp. open circuit HTL encoder
Encoder open-circuit monitoring (
1: Fault
Resp. max. speed/output freq. reached
0: No Reaction
Resp. to max. freq. feedb. DIG12/67
1: Fault
Parameters
Info
Lenze setting
Value Unit
Greyed out = display parameter