17
Function library
17.1
Function blocks | L_Curve_3
1339
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Outputs
Parameters
Designator
Data type
Value/meaning
nOut_a
INT
Output value (y)
• ±16384
≡
±100 %
• Internal limitation to ±32767 (±199.99 %)
When using the FB for tensile force characteristic
(from V12.00.00)
:
Current tensile force setpoint in [%]
• 16384
≡
100 %
bLimit
BOOL
"Limitation active" status signal
TRUE The output value is limited to ±199.99 %.
nCurveValue_a
INT
From version 12.00.00
Current characteristic value of the tensile force characteristic in [%]
Parameters
Possible settings
Info
-199.99
%
199.99 Output value
• Read only
Function selection
0 Out = 0
FB deactivated (Lenze setting)
1 Out = In
2 Out = f(In)
In preparation!
3 Out = f(table)
See description of
L_Curve_1
:
4 Out = f(characteristic)
Use of the L_Curve_3 for tensile
-199.99
%
199.99 Upper limit for input value
• Lenze setting: 199.99 %
-199.99
%
199.99 Lower limit for input value
• Lenze setting: -199.99 %
-32767
32767 X values for characteristic function
• Subcodes 1 ... 32 correspond to
interpolation point values
X1 ... X32.
• ±16384
≡
±100 %
• Lenze setting: 0
See description of
L_Curve_1
:
-32767
32767 Y values for characteristic function
• Subcodes 1 ... 32 correspond to
interpolation point values
Y1 ... Y32.
• ±16384
≡
±100 %
• Lenze setting: 0
See description of
L_Curve_1
: