
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
213
5
Motor control (MCTRL)
5.8
Sensorless control for synchronous motors (SLPSM)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.8.2
Types of control
Sensorless control for synchronous motors can only be executed in the "Speed control with torque
limitation" (
bTorquemodeOn
= FALSE) mode.
Speed control with torque limitation
A speed setpoint is selected and the drive system is operated in a speed-controlled manner. For
adapting the operational performance, the overload in the drive train can be limited:
• The torque is limited via the torque setpoint.
• The torque setpoint is identical to the value at the output of the speed controller,
nOutputSpeedCtrl
.
• To avoid overload in the drive train, the torque in motor mode can be limited via the
nTorqueMotLimit_a
process input signal, and the torque in generator mode can be limited via
the
nTorqueGenLimit_a
process input signal:
Designator
DIS code | data type
Information/possible settings
nTorqueMotLimit_a
| INT
Torque limitation in motor mode
• Scaling: 16384
≡
100 % M
max
(
)
• Setting range: 0 … +199.99 %
• If keypad control is performed: Parameterisable via
nTorqueGenLimit_a
| INT
Torque limitation in generator mode
• Scaling: 16384
≡
100 % M
max
(
)
• Setting range: -199.99 ... 0 %
• If keypad control is performed: Parameterisable via
Stop!
Torque limitation is only active in the closed-loop controlled operation (|n
Setpoint
| >
n
C00996
)!
• It must be prevented that the actual speed value is braked into the non-observable
area due to the torque limitation!
Note!
To avoid instabilities during operation, the torque limit values are internally processed
as absolute values.