17.1.134.2 Ramp function generator
The PID output is led via a ramp function generator with linear characteristic. This serves to transfer
setpoint step-changes at the PID output into a ramp which should be as steep as possible.
[17-60] Acceleration and deceleration times
• t
ir
and t
if
are the desired times for changing between w1 and w2.
• The ramps for acceleration and deceleration can be set individually.
•
: Acceleration time t
ir
•
: Deceleration time t
if
• The t
ir
/t
if
values are converted into the required Ti times according to the following formula:
• The ramp function generator is immediately set to "0" by setting
bInAct
to TRUE.
17.1.134.3 Operating range of the PID process controller
The value range of the input signal
nSet_a
and thus the operating range of the PID process controller
can be limited with the following parameters:
•
: Pos. maximum (default setting: 199.99 %)
•
: Pos. minimum (default setting: 0.00 %)
•
: Neg. minimum (default setting: 0.00 %)
•
: Neg. maximum (default setting: 199.99 %)