Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
801
14
Parameter change-over
14.4
Internal interfaces | System block "LS_WriteParamList"
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Outputs
Designator
Data type
Value/meaning
bDone
BOOL
"Writing of the parameter list completed" status signal
• The output is automatically reset to FALSE if writing via
bExecute
is activated
again.
TRUE Writing of the parameter list successfully completed.
FALSE The FALSE status can have the following meanings:
1.There is no active writing of the parameter list.
2.Writing of the parameter list has not been completed yet.
3.An error has occurred (if
bFail
= TRUE).
bFail
BOOL
"Error" status
TRUE An error has occurred (group signal).
• See display parameter
) for details.