15
Parameter reference
15.2
Parameter list
920
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00570
C00571
C00572
Parameter | Name:
C00570 | Resp. to controller limitations
Data type: UNSIGNED_8
Index: 24005
d
= 5DC5
h
Configuration of monitoring of the motor control (group 2)
Selection list
0 No Reaction
1 Fault
5 Warning
Subcodes
Lenze setting
Info
C00570/1
0: No Reaction
Response if direct-axis current controller is limited
• e.g. at servo control (
C00570/2
0: No Reaction
Response if cross current controller is limited
• e.g. at servo control (
C00570/3
0: No Reaction
Response if torque setpoint is limited
• Limitation of the speed controller output, the
differential setpoint precontrol, and of the additive
torque at (
) servo control and (
) sensorless
vector control.
C00570/4
0: No Reaction
Response if field controller is limited
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00571 | Resp. to wrong controller setting
Data type: UNSIGNED_8
Index: 24004
d
= 5DC4
h
From version 14.00.00
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes
Lenze setting
Info
C00571/1
6: Information
Resp. to: Motor control does not match motor data
C00571/2
1: Fault
Resp. to a non-set speed controller
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00572 | Brake resistor overload threshold
Data type: UNSIGNED_8
Index: 24003
d
= 5DC3
h
From version 02.00.00
Adjustable threshold for monitoring the brake resistor utilisation
• The response for reaching the threshold can be selected in
Setting range
(min. value | unit | max. value)
Lenze setting
0
%
100
100 %
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1