17
Function library
17.1
Function blocks | L_DFRFG_1
1345
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
17.1.72
L_DFRFG_1
This FB synchronises a drive (slave) to the master value of a master drive and then executes a
angular synchronism with regard to the digital frequency.
Inputs
Designator
Data type
Information/possible settings
bSetTPReceived
BOOL
Input for status signal "Touch probe detected"
FALSE
TRUE Touch probe or zero pulse received.
dnSetTPPos_p
DINT
Input for accepting the position measured via touch probe
nIn_v
INT
Speed setpoint of the master
• Scaling: 16384
≡
15000 rpm
bRfg0
BOOL
Ramp down ramp function generator to "0" (quick stop function)
• This input can, for instance, be connected to the status signal "quick stop active".
TRUE Ramp down the ramp function generator to "0"
• The drive is brought to a standstill with the deceleration time set
.
bRfgStop
BOOL
Stop ramp function generator
TRUE Stop ramp function generator
• The last status is output to
nOut_v
.
• The speed/angle setpoint
nIn_v
is saved.
• After
bStop
is reset to FALSE, the setpoint angle is approached via
the ramp function generator.
bReset
BOOL
Reset added angle setpoint
TRUE The internally added angle setpoint is reset and the ramp function
generator is activated. If the status signal
bFail
is set, it will also be
reset.
TRUE
FALSE Detect speed/angle setpoint.
/B')5)*B
Q2XWBY
E)DLO
&
& 6\QFGLU73IXQFW
&
& $FFGHFWLPH
& 'HFWLPH463
E6HW735HFHLYHG
GQ6HW733RVBS
E5IJ
E5IJ6WRS
E5HVHW
Q,QBY
E6\QF
6
5
4
& 6\QFZLQGRZ
& 2IIVHW
0D[VSHHGXS
)ROORZLQJHUURUOLPLW