Parameter reference
15.2
Parameter list
1150
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02867
Subcodes
Lenze setting
Info
C02866/1
1: Yes
Motor ident.: Current controller par. from C075 C076
•
From version 06.00.00
Automatic motor data identification
C02866/2
0: No
Motor phase error monitoring before operation
•
From version 11.00.00
Motor phase error monitoring before operation
C02866/3
0: No
Brake chopper DC-bus slave
•
From version 12.00.00
Control of multiple internal brake choppers in the DC-
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C02866 | MCTRL: Special settings
Data type: UNSIGNED_8
Index: 21709
d
= 54CD
h
Parameter | Name:
C02867 - Identification procedure
Data type: UNSIGNED_8
Index: 21708
d
= 54CC
h
From version 10.00.00
Selection of the identification procedure for motor parameter identification
Automatic motor parameter identification
Selection list
Info
0 automatic
Automatic selection of the optimum identification
procedure:
• For synchronous motors, the extended identification
procedure is always used.
• For asynchronous motors with a rated motor power
of up to 11 kW, the basic identification procedure is
used.
• For asynchronous motors with a rated motor power
of more than 11 kW, the extended identification
procedure is used.
1 standard identification
• Only for asynchronous motors.
• Duration approx. 30 s
2 extended identification
• Stands out due to increased accuracy of the
determined motor parameters.
• Also supports synchronous motors and asynchronous
motors with a power of more than 11 kW.
• Duration approx. 80 s
Subcodes
Lenze setting
Info
C02867/1
0: automatic
Motor parameter identification: Process
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1