155
5
Motor control (MCTRL)
5.3
Defining current and speed limits
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Current limitation in motor and generator mode
In the various motor control modes, the inverter is provided with functions which determine the
dynamic behaviour under load and counteract exceedance of the maximum current in motor or
generator mode.
The current limits must be selected depending on
• the permissible maximum current of the motor
recommendation: I(Mot)
N
< 1.5 ... 2.0
• the permissible maximum current of the inverter
• the torque in motor/generator mode required for the application
Parameters
Info
Lenze setting
Value Unit
Imax in motor mode
47.00 A
Imax in generator mode
• 100 %
≡
Imax in motor mode (
)
100 %
Note!
Highly dynamic applications
(that have e.g. too short acceleration/deceleration times or excessively changing loads)
The overcurrent disconnection may respond (fault message oC1 or oC11) if the setting of
the maximum current in motor mode in
approximately corresponds to the
maximum permissible value of the respective inverter.
Remedies:
• Increase of the acceleration and deceleration ramp times
• Reduction of the maximum current in motor mode
)
• Reduction of the maximum current in generator mode (
)
• Adaptation of the indirect peak current limitation (procedure depends on the selected
motor control mode, see below)
• Reduction of the reset time of the current limiting controller (
Influencing the torque in motor/generator mode
The torque in motor and generator mode can be limited via the
nTorqueMotLim
and
nTorqueGenLim
process signal inputs.
• If V/f characteristic control (VFCplus) is selected, limitation is indirectly performed via
a so-called I
max
controller.
• If sensorless vector control (SLVC), sensorless control for synchronous motors (SLPSM)
or servo control (SC) is selected, limitation has a direct effect on the torque-producing
current component.
If keypad control is selected, the
nTorqueMotLim
and
nTorqueGenLim
process signals can
be parameterised via
.