Parameter reference
15.2
Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00597
C00598
C00599
Parameter | Name:
C00597 | Resp. to motor phase failure
Data type: UNSIGNED_8
Index: 23978
d
= 5DAA
h
Response to motor phase failure
• If a phase current does not exceed the threshold set in
for more than one period, the response set here
will be triggered.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00598 | Resp. to open circuit AINx
Data type: UNSIGNED_8
Index: 23977
d
= 5DA9
h
Configuration of monitoring of the analog inputs
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
5 Warning
Subcodes
Lenze setting
Info
C00598/1
3: TroubleQuickStop
Response to open circuit at AIN1 if configured as
4 ... 20 mA current loop
C00598/2
3: TroubleQuickStop
Response to open circuit at AIN2 when being configured
as 4 ... 20 mA-current loop
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00599 | Motor phase failure threshold
Data type: INTEGER_16
Index: 23976
d
= 5DA8
h
Threshold for motor phase failure monitoring
• 100 %
≡
rated inverter current (
• If a phase current does not exceed the threshold set here for more than one period, the response to motor phase
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
100.00
5.00 %
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100