Parameter | Name:
C00104 | Quick stop setting
Data type: UNSIGNED_16
Index: 24471
d
= 5F97
h
Parameter | Name:
C00105 | Decel. time - quick stop
Data type: UNSIGNED_32
Index: 24470
d
= 5F96
h
The set deceleration time determines the ramp slope at quick stop
Activate/deactivate quick stop
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.900
2.000 s
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00106 | Auto DCB: Hold time
Data type: UNSIGNED_32
Index: 24469
d
= 5F95
h
Hold time of the automatic DC injection brake
• The DC injection brake is applied for the time set here if the value falls below the speed setpoint set in
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.000
0.500 s
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00107 | DC braking: Hold time
Data type: UNSIGNED_32
Index: 24468
d
= 5F94
h
Maximum hold time of the manual DC injection brake
• A time can be set here after which the DC injection brake is switched off automatically to prevent the motor from
thermal overload.
• When "999.000 s" is set, the hold time is infinite.
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.000
999.000 s
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000