Basic drive functions (MCK)
8.4
Basic settings
542
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Status "Done" (
)
• The position setpoint has reached the target position.
Status "DwellTime" (
)
• Bit 16 in the
bDwellTime
output of the
FB is set
when the setpoint position has been reached after the dwell time set in
has expired.
• The status detects the time after the
bDone
signal when settling to target position is executed
and actual position detection is not active yet.
Status "InTarget" (
)
• If the actual position is within the symmetrical target position window after the dwell time has
expired, bit 17 is set to "1" in the
or the
bInTarget
output of the
• The "InTarget" status is reset if:
• the motor shaft leaves the target position window,
• a new profile or a new motion process is started,
•
bInTarget
has been set via manual jog (intermediate stops) and the "
" mode is left,
• the target position window has been left in the "
" mode and a speed setpoint
not equal to "0" is injected into the process,
• a new homing process starts,
• the reference is set,
• the device is switched off/on.
Note!
• The target position including the target position window has to be within the
maximum traversing range.
• Please observe the following if you use
bInTarget
as stepping condition in a step
sequence:
The
bInTarget
signal needs the set position to be located in the target. A profile restart
immediately deletes the setpoint position in the first cycle and thus also resets
bInTarget
.