Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
911
15
Parameter reference
15.2
Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00490
C00495
C00488/3
0: Level
InputSens.SlowDown2
• Selection of edge or level for starting slow-down
function 2
C00488/4
0: Level
InputSens.Stop2
• Selection of edge or level for stop function 2
C00488/5
0: Level
InputSens.SlowDown3
• Selection of edge or level for starting slow-down
function 3
C00488/6
0: Level
InputSens.Stop3
• Selection of edge or level for stop function 3
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00488 | L_JogCtrlEdgeDetect
Data type: UNSIGNED_8
Index: 24087
d
= 5E17
h
Parameter | Name:
C00490 | Position encoder selection
Data type: UNSIGNED_8
Index: 24085
d
= 5E15
h
Selection of the feedback system for the generation of the actual position on the load
Selection list
(Lenze setting printed in bold)
Info
0 No sensor: nSpeedSetValue_a
No encoder available on the load.
The position signal
dnMotorPosAct_p
is derived from the
speed setpoint
nSpeedSetValue_a
.
1 Sensor signal FreqIn12
Position encoder signal is fed via digital inputs DI1 and
DI2
2 Encoder signal FreqIn67
Position encoder signal is fed via digital inputs DI6 and
DI7
5 Encoder signal FreqIn1267
From version 15.00.00
Position encoder signal is fed via digital inputs DI1/DI2
and DI6/DI7 (connection of 4-track HTL encoders)
10 Encoder selection C495 or
nVoltageAngleAct_a
From version 12.00.00
The position signal
dnMotorPosAct_p
is either calculated
from the set speed feedback (for
> 0) or from the
speed signal
nMotorSpeedAct_v
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00495 | Speed sensor selection
Data type: UNSIGNED_8
Index: 24080
d
= 5E10
h
Selection of the feedback system for the actual speed for motor control and display
Selection list
(Lenze setting printed in bold)
Info
0 No sensor
No sensor available for the actual speed detection
1 Sensor signal FreqIn12
Speed sensor signal is fed via the digital DI1 and DI2
inputs
2 Encoder signal FreqIn67
Speed encoder signal is fed via digital inputs DI6 and DI7
5 Encoder signal FreqIn1267
From version 15.00.00
Speed encoder signal is fed via digital inputs DI1/DI2 and
DI6/DI7 (connection of 4-track HTL encoders)
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1