Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
865
15
Parameter reference
15.2
Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00242
C00243
C00244
C00245
Parameter | Name:
C00242 | L_PCTRL_1: Operating mode
Data type: UNSIGNED_8
Index: 24333
d
= 5F0D
h
The
FB: Selection of the operating mode
• Depending on the selection, the blue switches in the displayed signal flow are set accordingly in the Engineer on
the
Application parameters
tab for the
Selection list
(Lenze setting printed in bold)
Info
0 Off
The input setpoint
nNSet_a
is output without any
changes at the output
nOut_a
.
1 nNSet + nNSet_PID
nNSet_a
and
nAct_a
are used as PID input values. The
arriving
nNSet_a
is additively linked to the value output
by the PID element.
2 nSet_PID
nSet_a
and
nAct_a
are used as PID input values. The
input
nNSet_a
is not considered.
3 nNSet_PID
nNSet_a
and
nAct_a
are used as PID input values. The
input
nSet_a
is not considered.
4 nNSet + nSet_PID
nSet_a
and
nAct_a
are used as PID input values. The
arriving
nNSet_a
setpoint is additively linked to the value
output by the PID element.
5 nNSet || nSet_PID
nSet_a
and
nAct_a
are used as PID input values. The
setpoint
nNSet_a
is output at the output
nOut_a
. The
PID output value is output at the output
nPIDOut_a
.
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00243 | L_PCTRL_1: Acceleration time influence
Data type: UNSIGNED_32
Index: 24332
d
= 5F0C
h
The
FB: Acceleration time for showing the PID output value
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.999
5.000 s
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00244 | L_PCTRL_1: Deceleration time influence
Data type: UNSIGNED_32
Index: 24331
d
= 5F0B
h
The
FB: Deceleration time for masking out the PID output value
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.999
5.000 s
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00245 | L_PCTRL_1: PID output value
Data type: INTEGER_16
Index: 24330
d
= 5F0A
h
The
FB: Display of the output value of the PID process controller
Display range
(min. value | unit | max. value)
-199.99
%
199.99
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100