Parameter reference
15.2
Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00142
C00144
C00148
Subcodes
Info
C00138/1
SYS control signals
C00138/2
MCK control signals
C00138/3
FWM control signals
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Parameter | Name:
C00138 | Internal control signals
Data type: UNSIGNED_16
Index: 24437
d
= 5F75
h
Parameter | Name:
C00142 | Auto-start option
Data type: UNSIGNED_8
Index: 24433
d
= 5F71
h
Starting performance of the inverter after mains connection, undervoltage, loading of the Lenze setting as well as
a reset of "Trouble" or "Fault" can be parameterised individually.
Automatic restart after mains connection/fault...
Setting range
(min. hex value | max. hex value)
Lenze setting
0x00
0xFF
0x19
(decimal: 25)
Value is bit-coded: (
= bit set)
Info
Bit 0
Inhibit at power-on
Bit 1
Inhibit at trouble
Bit 2
Inhibit at fault
Bit 3
Inhibit at undervoltage
Bit 4
Inhibit at Lenze setting
From version 06.00.00
Bit 5
Reserved
Bit 6
Reserved
Bit 7
Reserved
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Parameter | Name:
C00144 | Switching freq. reduct. (Temp.)
Data type: UNSIGNED_8
Index: 24431
d
= 5F6F
h
Activation of the automatic switching frequency reduction if the temperature is too high
Selection list
(Lenze setting printed in bold)
Info
0 Off
Automatic switching frequency reduction deactivated
1 On
Automatic switching frequency reduction activated
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00148 | LS_DriveInterface: Error message config.
Data type: UNSIGNED_16
Index: 24427
d
= 5F6B
h
From version 04.00.00
Selection of the device statuses for which the
bCollectedFail
group error output of SB
is to be set
to TRUE.
Setting range
(min. hex value | max. hex value)
Lenze setting
0x0000
0xFFFF
0x0030
(decimal: 48)
Value is bit-coded: (
= bit set)
Info
Bit 0
SafeTorqueOff
Bit 1
ReadyToSwitchOn