HLP-A100 Series Operating Manual
HLP-A100 Series
-
78
-
C03.41 Function Description
Range
Unit
Default Setting
Ramp1Ramp up Time
0.05~3600.00
S
*
Function: Enter the ramp-up time f rom 0 Hz to rated Motor speed in C01.25.
Attention: Choose a rame-up time such that the output current does not
exceed the current limit in C04.18.
Binary system
bit1
bit0
Ramp Group
Terminal State
0
0
1
0
1
2
1
0
3
1
1
4
C03.42 Function Description
Range
Unit
Default Setting
Ramp1 Ramp Down
Time
0.05~3600.00
S
*
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.50 Function Description
Range
Unit
Default Setting
Ramp2 Type
0~2
0
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration..
C03.5* Ramp2