HLP-A100 Series Operating Manual
HLP-A100 Series
-
146
-
disappeared, drive will ramp to dwell stage and wait for wobble
cycle start command to end dwell stage. In auto mode, there are
running on center f requency and running on dwell f requency two
ways to select for wobble reset. But in manul mode, only running
on center f requency can be achieved .
Function: During dwell stage, the drive will run on this f requency, until
when wobble cycle start command issued or dwell time has been
used up.
C30.01 Function Description
Range
Unit
Default Setting
Dwell Frequency
0.000-200.000 Hz
0.000
Function: When wobble start mode selecte Auto[0](C30.00=0), the drive runs
on dwell f requency(C30.01=0) in the period of the time set in this
parameter.
C30.02 Function Description
Range
Unit
Default Setting
Dwell Time
0.0~3600.0
s
0.0
C30.10 Function Description
Range
Unit
Default Setting
Centre Frequency Rate 0.000~30.000 Hz
0.500
Function: When Center Frequency Mode select Auto Dcrease[1](C30.12=1), this
parameter used to set the dcrease rate for center f requency. And the
center f requency can be defined via analog input
、
preset reference
or local bus.
C30.12 Function Description
Range
Unit
Default Setting
Centre Frequency Mode
0~1
0
Option: [0]: Fixed, center f requency is unchangable ;
[1]: Auto Decrease, center f requency of auto decrement.
Function: If [1] is selected, center f requency will decrease by the “Center
C30.11 Function Description
Range
Unit
Default Setting
Centre Frequency
Low Limit
0.000~200.000 Hz
10.000
Function: When Center Frequency Mode select Auto Dcrease[1](C30.12=1), this
parameter used to set the low limit of the center f requency.
C30.1* Wobble Cycle