HLP-A100 Series
HLP-A100 Series Operating Manual
-
45
-
Item Parameter
No.
Function
Description
Setting range
Unit
Default
setting
Page
No.
Pa
ram
ete
r G
rou
p 14
: S
pec
ial
Fu
nc
tio
ns
C14.23 Trip Lock
0: Disable, Trip lock
fault reset do not
need power off;
1: enable, Trip lock
fault reset need
power off;
1
C14.27
Action At
Inverter Fault
0: Trip; 1: Warning;
0
120
C14.30
Current
Limit Control,
Proportional
Gain
0~500
100
C14.31
Current
Limit Control,
Integration
Time
0~2
0.02
C14.32
Current Limit
Control, Filter
Time
1~100
1
*C14.40 VT Level
40-90
%
90
120
*C14.41
AEO
Minimum
Magnetisation
40~75
%
66
120
C14.50 RFI Filter
Switch
0: Off 1:On
2:Reserved
1
*C14.51
DC-Link
Voltage
Compensation
0: Off; 1: On;
1
120
C14.52 Fan Control
0: Auto; 4:Run in
low temperature;
5-8: Reserved;
0
*C14.55 Output Filter
0: Off; 1: Sine-Wave
Filter; 3: Sine-Wave
Filter with feedback;
0
121
*C14.63
Min Switch
Frequency
2~6: 2kHz~6kHz;
7: 8kHz; 8: 10 kHz;
9: 12kHz; 10: 16kHz;
2
121