HLP-A100 Series
HLP-A100 Series Operating Manual
-
173
-
44
Reserved
45
No voltage warning
Voltage warning
46
Not in current limit
Current limit
47
No thermal warning
Thermal warning
Register
Description
00000-00006
Reserved
00007
The most recent error code from FC data interface
00008
Parameter index
00009-00989 Parameter group 00
00999-01989
Parameter group 01
01999-02989
Parameter group 02
…
…
15999-16989
Parameter group 16
Field
Description
01
FC address
01
Funtion
00 30
Coil address (ADDRH ADDRL).0x0030 convert to decimal
number is 48. Coil address 49 is frequency converter output
frequency.
00 10
Data bits number is 16. 0x 0010 convert to decimal number is
16
3D C9
CRC check
The relationship between register address and parameter number is:
register address = parameter number × 10 -1
Example
:
Detect inverter output frequency
Transmit
:
01 01 00 30 00 10 3D C9
(
Hexadecimal
)
Receive
:
01 01 02 00 20 B8 24
(
Hexadecimal
)
12.3 Read Coil Status