HLP-A100 Series Operating Manual
HLP-A100 Series
-
104
-
C07.30
Function Description
Range
Unit
Default Setting
Process PI Normal/
Inverse Control
0~1
0
Option: [0] Normal, f requency converter is to reduce/increase the output
f requency if the feedback signal is larger/lower than reference;
[1] Inverse, f requency converter is to reduce/increase the output
f requency if the feedback signal is larger/lower than reference;
C07.31
Function Description
Range
Unit
Default Setting
Process PI Anti Windup
0~1
1
Option: [0] Disable, continue regulation of a given error even when the output
f requency can’t be increased/decreased.
[1] Enable, ceases regulation of a given error when the output
f requency can’t be increased/decreased.
Function: This f unction ensures the output f requency reaches to f requency
limit. PI-controller will be initialized to the current f requency when
the output f requency can not be changed. This can prevent the
integrator continue to integrate on an error when the PI-controller
can’t adjust output f requency.
C07.32
Function Description
Range
Unit
Default Setting
Process PI Start Speed
0.0~200.0
Hz
0.0
Function: Enter the motor speed to be attained as a start signal for
commencement of PID control . When the power is switched on,
the f requency converter will commence ramping and then operate
under speed open loop control. Thereaf ter, when the Process PI
Start Speed is reached, the f requency converter will change over to
Process PI Control.