HLP-A100 Series
HLP-A100 Series Operating Manual
-
69
-
VI;
[6] Digital input DI4, Connect thermistor to digital input
terminal DI4;
Function: Select the thermistor input terminal.
Attention: Analog input can’t be selected for other purpose when selected
as thermistor resource.
Digital input DI4 can’t be selected for other purpose when selected
as thermistor resource.
Thermistor specifications:
Input signal type
Voltage Supply
Termistor threshold
Digital
10V
<0.8kΩ , >2.9kΩ
Analog
10V
<0.8kΩ , >2.9kΩ
C02.00 Function Description Range
Unit
Default Setting
DC Hold Current
0~150
%
50
Function: This parameter either holds the motor (holding torque) or
preheats the motor. This parameter is active if DC Hold has been
selected in either C01.72 start function or C01.80 Function at
Stop.
Description of Choice: Enter a value for holding current as a percentage
of the rated motor current set in par. C01.24 Motor Current.
100% DC holding current corresponds to IM,N.
Attention: Avoid 100% current too long as it may overheat the motor.
C02.01 Function Description Range
Unit
Default Setting
DC Brake Current
0~150
%
50
Function: This parameter is used for setting the DC brake currents that is
set as a percentage value of the rated motor current IM, N set in
C01.24.
Description of Choice: Parameters related to the DC brake current are as
follows:
DC-brake command, see C05.1* choice (5);
DC brake cut in speed, see C02.04;
C02.0* DC -Brake
6.3 Parameter Group 02: Brakes