HLP-A100 Series Operating Manual
HLP-A100 Series
-
66
-
C01.63
Function Description
Range
Unit
Default Setting
Slip Compensation
Time Constant
0.05~5.00
S
0.10
Function: Enter the slip compensation reaction speed. A high value
results in slow reaction, and a low value results in quick reaction.
If low-frequency resonance problems arise, use a longer time
setting.
C01.64
Function Description
Range
Unit
Default Setting
Resonance Dampening
0~500
%
50
Function: High-frequency resonance problems between motor and the
frequency converter can be eliminated by setting this parameter.
C01.65
Function Description
Range
Unit
Default Setting
Resonance Dampening
Time constant
0.005~0.050
S
0.005
Description of choice: Choose a time constant that provides the best
dampening.
C01.7* Start Adjustments
C01.71
Function Description
Range
Unit
Default Setting
Start Delay
0.0~10.0
S
0.0
Function: This parameter enables a delay of the starting time. The
frequency converter begins with the start function selected in
par. 1-72. Set the start delay time until acceleration is to begin.
Attention: Setting start delay to 0.0 sec. disables Start Function, [C01.72],
when start command is given.
C01.72
Function Description
Range
Unit
Default Setting
Start Function
0~2
2
Option: [0] DC Hold/delay time;
[2] Coast/delay time;
Function: Select [0], Motor is energized with DC holding current (par.
C02.00) during start delay time; Select [2], Motor is coasted
during start delay time (inverter off).