HLP-A100 Series
HLP-A100 Series Operating Manual
-
73
-
C03.07
Function Description
Range
Unit
Default Setting
Actual reference
calculation
0~1
0
Option: [0] Preset ref Reference source 1,2,3
[1] Preset reference priority
Description of Choice:
[0], Actual reference = Preset ref Reference source 1,2,3
[1], When using preset reference 1-N, actual reference = preset
reference [1-N], else actual reference = preset reference [0] +
reference source 1,2
C03.10 Function Description
Range
Unit
Default
Setting
Preset Reference
-100.00~100.00[16]
%
0.00
C03.1** References
Function: This parameter is an array-16 to be used for presetting different
references.
Description of Choice: When C03.00 select “1”(-Min~Max), 100%= value
set in C03.03; When C03.00 select “0”(Min~Max), for example,
If C03.02 is set to “20” and C03.03 is set to 50, 0
%=
0 and 100
%
=
50; If C03.02 is set to “-70”, and C03.03 is set to 50, 0
%=
0
and 100
%=
70.
Each parameter set-up contains 16 preset references which are selectable
via digital terminals or local bus. See C05.1*.
Selection of preset reference indicates with a four-digital binary code. If
the f requency converter detects the corresponding terminals connected, then
the bit is “1”, otherwise, the bit is “0”. Digital input terminal
、
binary code and
the corresponding relationship between pre-set values as follows: