HLP-A100 Series Operating Manual
HLP-A100 Series
-
18
-
Symbol
Description
Specification
Digital output
(DO1
、
DO2) Digital output
1
、
Open collector output;
2
、
Output current range: 0-50mA;
3
、
Max voltage 30V;
4
、
Two different way to connect relay:
V D D
D O
1
D O
2
D C M
C O M
R e la y
1
R e la y
2
Note: DCM and COM must be connected.
V D D
D O
1
D O
2
D C M
C O M
+ +
S u p p ly
R e la y
1
R e la y
2
Digital output
common
terminal
(DCM)
Digital output
common
terminal
Connect COM as Digital output reference
ground while use.
Analog output
(VO
、
AO)
Analog output
VO can be selected to the current output
or voltage output via jumper switch
in the control board. AO can only be
selected as current output:
1
、
Output mode: 0-20mA or 0-10V;
2
、
Voltage output: Load larger than
500Ω;
3
、
Current output: Load larger than
500Ω;
Pulse output
DO1
Pulse output
DO1 can also be configured as pulse
output channels:
1
、
Pulse output range: 0.001-5.000KHz
(range f rom 0.001-100.000KHz is optional);
2
、
Voltage range: 0-24V;
3
、
Duty ratio: 40%-60%;
4
、
Resistive load >1kΩ, capacitive load <
10nF;