HLP-A100 Series
HLP-A100 Series Operating Manual
-
59
-
*C01.00 Function Description Range
Unit
Default Setting
Configuration Mode
0~3
0
Option: [0] Speed open loop,for general applications;
[3] Process closed loop,feedback signal is a process unit, such as:
pressure
、
temperature etc. When process closed loop is selected,
the motor can only run clockwise. For detailed parameter
settings, please refer to C07.3*.
[4] Torque Open loop, this mode is only effective in VVC+. For
detailed parameter settings, please refer to C07.1*.
Attention: If configuration mode is changed, C03.00, C03.02, C03.03 will
be restored to factory setting.
*C01.01 Function Description Range
Unit
Default Setting
Control Principle
0~1
1
Option: [0] V/F, used for parallel connected motors or special motors, V/
F settings are set in C01.55 and C01.56 separately;
[1] VVC+, used on applications that needs torque compensation
at low frequency or higher requirements on control performance.
Description of choice: Before V/F or VVC+ control, perform AMA first
to get correct motor data.
Attention: When V/F control mode is selected, slip compensation and
load compensation are invalid; When VVC+ control mode is
selected,it includes slip compensation and load compensation
itself.
*C01.03 Function Description
Range
Unit
Default Setting
Torque Characteristics
0~3
0
Option: [0] Constant torque, used for constant torque load;
[1] Variable torque, used for variable torque load, such as fan
applications
、
centrifugal pump etc;
[3]Auto Energy optimization, see C14.41 AEO minimum
magnetisation.
C01.0* General Settings
change the parameter settings.
Attention: Main Menu Password function is only valid to LCP, not active
to local bus.
6.2 Parameter Group 01: Load and Motor