HLP-A100 Series
HLP-A100 Series Operating Manual
-
93
-
C05.58 Function Description
Range
Unit
Default
Setting
Terminal DI4 High
Ref. /feedback
4999.000~4999.000
50.000
Function: Enter high ref./feedback corresponding to value in C05.56.
C05.59 Function Description
Range
Unit
Default Setting
Terminal DI4 Filter
Time Constant
1~1000
ms
100
Function: Enter the pulse filter time constant, the low pass filter reduces the
influence on and dampends the oscillations on the feedback signal
f rom the control. This parameter can’t be changed when motor is
running.
C05.60
Function Description
Range
Unit
Default Setting
DO1 Pulse Output
0~23
0
Option: [0] Digital Output, see C05.30;
[10] Output f requency, 0.020-50.000KHz Corresponding to 0-200Hz;
[11] Reference, C03.00 select“0” [Min – Max] , 0% = 0.020KHz, 100% =
50.000KHz; C03.00 select“1” [-Max – Max] , -100% = 0.020KHz, 100%
= 50.000KHz;
[12] Feedback, 0.020-50.000KHz corresponding to -200% ~ 200%;
[13] Motor current, 0.020-50.000KHz corresponding to 0-Max. motor
current, see par. C16.37;
[16] Power, 0.020-50.000KHz corresponding to 0-Motor current, see
C01.20;
[17] Speed, 0.020-50.000KHz corresponding to 0-Motor speed, see
C01.25;
[18] Motor voltage, 0.020-50.000KHz corresponding to 0-Motor
voltage, see C01.22;
[20] Bus control: 0.020-50.000KHz corresponding to 0.0% - 100.0%,
100% equals to settings in C03.03;
[21] Pulse input, 0.020-50.000KHz corresponding to reference in
C05.55-C05.56 entered via DI4;
[22] Values on analog input VI, 0.020-50.000KHz corresponding to
references in C06.10
、
C06.12 and C06.11
、
C06.13;
[23] Values on analog input AI, 0.020-50.000KHz corresponding to
C05.6* Pulse Output