HLP-A100 Series
HLP-A100 Series Operating Manual
-
87
-
[1] Reset, reset the f requency converter af ter a Trip/Alarm;
[2] Coast Inverse, no output, leaving the motor coasting to stop;
[3] Coast and reset Inverse, the f requency converter resets leaving the
motor coasting to stop.
[4] Quick stop Inverse, generates a stop in accordance with the quick-
stop ramp time set in C03.81;
[5] DC-brake Inverse, see C02.01, this f unction is only active when
value in C02.02 and C02.04 are different f rom 0.
[6] Stop Inverse, the drive is stopped according to selected ramp time;
[8] Start, 1=start, 0=stop;
[9] Pulse start, motor starts if a pulse signal (pulse with of not less
4ms) is received.
[10] Reversing, change direction of motor shaf t rotation, reversing
signal only changes direction of rotation, it does not activate start
f unction, C04.10 must choose [2] Both directions;
[11] Start reversing, used for start/stop and for reversing at the same
time;
[12] Enable start forward only, the motor can only run clockwise
direction;
[13] Enable start reverse only, motor can only run counter clockwise
direction;
[14] Jog, used for activating jog speed, see C03.11;
[15] Preset ref. bit0, Preset ref.bit0
、
bit1
、
bit2
、
bit3 is used for the choice
of the preset reference, see parC03.10;
[16] Preset ref. bit1, same as[15];
[17] Preset ref. bit2, same as [15];
[18] Preset ref. bit3, same as [15];
[19] Freeze reference, the f rozen reference is the start point of up/
down when Speed up and Speed down to be used. If Speed up/down
is used, speed change always follows ramp 2 in the range par. C03.02
Minimum Reference - par. C03.03 Maximum Reference. If f reezing
reference is active, stop the f requency converter via a terminal
programmed for to [2] Coast Inverse or [3] Coast and reset , inverse ;
[20] Freeze output, the f rozen reference is the start point of up/down
when Speed up and Speed down to be used. If Speed up/down is
used, the speed change always follows ramp 2 in the range 0 - Motor
rated f requency;
[21] Speed up, Activate this f unction by selecting either Freeze
reference or Freeze output. When Speed up is activated for less than
400 ms. the resulting reference will be increased by 0.1%. If Speed up
is activated for more than 400 ms. the resulting reference will ramp
according to ramp 2 ;
Summary of Contents for HLP-A100 Series
Page 1: ......
Page 2: ...HLP A100 Series Operating Manual...
Page 3: ......
Page 7: ...HLP A100 Series Operating Manual HLP A100 Series 6...