HLP-A100 Series Operating Manual
HLP-A100 Series
-
128
-
C16.02
Function Description
Range
Unit
Default Setting
Reference (%)
-200.0~200.0
%
Function: View total remote reference in percentage, the total reference is
sum of pulse, analog, preset, LCP Potmeter, local bus and f reeze
reference.
C16.03
Function Description
Range
Unit
Default Setting
Status Word
0~65535
%
Function: View active status word, the following shows the def inition for
each bit.
C16.04
Function Description
Range
Unit
Default Setting
Active Set-up
0~2
%
Function: View the drive active set-up. Select 0 indicates set-up 1, Select 1
indicates set-up 2, and select 2 indicates multi-set-up.
Communication Status Word
bit
0
1
bit00
Control not ready
Control Ready
bit01
Drive not ready
Drive ready
bit02
Coasting
Enabled
bit03
No Error
Trip
bit04
Error
Error without trip
bit05
Undefined
Undefined
bit06
No Error
Trip
bit07
No Warning
Warning
bit08
Not on reference
On reference
bit09
Local Control
Remote Control
bit10
Frequency not in range
Frequency in range
bit11
Stop
Running
bit12
Brake resistor is normal
Brake resistor fault
bit13
Voltage limit
Out of voltage limit
bit14
Undefined
Undefined
bit15
No terminal warning
Terminal warning