HLP-A100 Series
HLP-A100 Series Operating Manual
-
95
-
C05.7* Encoder Input
*C05.70
Function Description
Range
Unit
Default Setting
Encoder per Revolution
256~4096
1024
Function: Encoder resolution (pulses for each revolution of the motor shaf t,
see C05.70) is determined by the maximum f requency of receiving
pulses of the PG card (up to 205KHZ). According to the encoder
resolution and speed (rpm), in accordance with the following
formula F= C05.70×RPM/60 , the output f requency can be
calculated.
*C05.71
Function Description
Range
Unit
Default Setting
Encoder Direction
0~1
0
Function: Select [0] clockwise, or select [1] counter clockwise. Change the
detected encoder rotation without changing the wire to the encoder.
This parameter can not be changed while the motor is running.
Function: Enter the live Zero Time-out Time period, Live Zero Time-out
Time is active for analog inputs. If the analog signal interrupts
for the time period longer than the time set in this parameter, the
f unction selected in C06.01Live Zero Timeout Function will be
activated.
Description of Choice: If the analog input signal is back to normal within the
delay time, then, reset the timer.
C06.0* Analog I/O Mode
C06.00
Function Description
Range
Unit
Default Setting
Live Zero Timeout Time
1~99
S
10
Option: [0] Off;
[1] Freeze output, f rozen at the present value;
[2] Stop, overruled to stop;
[3] Jogging, overruled to jog speed;
[4] Max. speed, overruled to Max.speed;
[5] Stop and trip, overruled to stop with subsequent trip.
C06.01
Function Description
Range
Unit
Default Setting
Live Zero Timeout Func.
1~5
0