HLP-A100 Series
HLP-A100 Series Operating Manual
-
101
-
C06.81
Function Description
Range
Unit
Default
Setting
LCP Potmeter Low Ref. -4999.000~4999.000
0.000
[22] Value on analog input VI, (0-10V) or (0/4-20mA) corresponding
to references f rom C06.10
、
C06.12 to C06.11
、
C06.13;
[23] Value on analog input AI, (0-10V) or (0/4-20mA) corresponding
to references f rom C06.20
、
C06.22 to C06.21
、
C06.23;
Function: Select choices of the analog output VO.
C06.73
Function Description
Range
Unit
Default Setting
Terminal VO Output
Min Scale
0.00~200.00
%
0.00
Function: Scale minmum output of selected ananlog signal at terminal VO as
percentage of maximum signal value. See fig. below:
C06.74
Function Description
Range
Unit
Default Setting
Terminal VO Output
Max Scale
0.00~200.00 %
100.00
Function: Scale maximum output of selected analog signal at terminal VO as
percentage of maximum signal value.
C06.8* LCP Potmeter
The LCP potmeter can be select either as reference resource or relative
reference resource.
Function: This reference value corresponding to potentiometer turned f ully
counterwise .